Chapter 1

Introduction

The Extended Battery Module (EBM) can be added to the
Powerware

®

9140 uninterruptible power system (UPS) to extend the

available battery time (see Table 1). Up to four EBMs can be installed
with the Powerware 9140 UPS.

Table 1. Battery Runtimes (in Minutes)

Load

(10 kVA Models)

UPS Internal

Batteries

+1 EBM

+2 EBMs

+3 EBMs

+4 EBMs

100% Load

5

12

27

35

45

75% Load

7

17

35

46

60

50% Load

12

27

52

69

90

25% Load

31

61

99

138

181

Load

(7.5 kVA Models)

UPS Internal

Batteries

+1 EBM

+2 EBMs

+3 EBMs

+4 EBMs

100% Load

8.5

23.5

37.5

53

65.5

75% Load

12

30

52

69

86.5

50% Load

22

51.5

78.5

98.5

111

25% Load

48

94

116

>120

>180

NOTE Battery times are approximate and vary depending on the load configuration and battery charge.