SMA SC 500CP-US-10 600V User Manual
Page 82

11 Troubleshooting
SMA America, LLC
82
SCCP-US-BE-US_en-52
Operating Manual
3601
Leakage current to ground has occurred in
the PV array or the threshold defined in
parameter RisoCtlWarn has been
reached.
W
W
‒
• Check the grounding and
equipotential bonding.
• Check the module wiring and
PV system design.
• Check the RisoCtlWarn
parameter.
3803
The DC current of the PV array is too high. 1 min
D
x
• Check the DC input current.
• Check the module wiring and
plant design.
4003
Reverse currents detected in the PV array
or DC connection polarity is reversed.
30 s
A
‒
• Check PV modules for short
circuits.
• Check the module wiring and
plant design.
• Make sure the DC terminals
have the correct polarity.
Error no.
Explanation
Behavior of the
inverter
Corrective measures
S 1
S 2
R