SMA SC 500CP-US-10 600V User Manual
Page 92

13 Parameters
SMA America, LLC
92
SCCP-US-BE-US_en-52
Operating Manual
Limitation of the reactive
power of the inverter
0 kVAr to 550 kVAr
SC 500CP-US-10
550 kVAr
0 kVAr to 550 kVAr
SC 500CP-US-10 600V
550 kVAr
0 kVAr to 700 kVAr
SC 630CP-US-10
700 kVAr
0 kVAr to 792 kVAr
SC 720CP-US-10
792 kVAr
0 kVAr to 825 kVAr
SC 750CP-US-10
825 kVAr
0 kVAr to 880 kVAr
SC 800CP-US-10
880 kVAr
0 kVAr to 935 kVAr
SC 850CP-US-10
935 kVAr
0 kVAr to 990 kVAr
SC 900CP-US-10
990 kVAr
Limitation of the reactive
power of the Sunny
Central in the operating
state "Q at Night"
The reactive power
cannot exceed Qlimit.
0 kVAr to 300 kVAr
SC 500CP-US-10
300 kVAr
0 kVAr to 300 kVAr
SC 500CP-US-10 600V
300 kVAr
0 kVAr to 378 kVAr
SC 630CP-US-10
378 kVAr
0 kVAr to 432 kVAr
SC 720CP-US-10
432 kVAr
0 kVAr to 450 kVAr
SC 750CP-US-10
450 kVAr
0 kVAr to 480 kVAr
SC 800CP-US-10
480 kVAr
0 kVAr to 510 kVAr
SC 850CP-US-10
510 kVAr
0 kVAr to 540 kVAr
SC 900CP-US-10
540 kVAr
PFAbsMin*
Limitation of the
displacement power
factor cos φ
0.5 to 1
‒
0.8
Name
Description
Value/range
Explanation
Default
value