Inspection

SMA

Technologie AG

12

ESS-BEN074812

User manual

5 Inspection

Check the Electronic Solar Switch for wear before plugging it in.
Check if the metal tongues inside the plug show brown discolorations.

The Electronic Solar Switch can no longer safely disconnect the DC side if one of the
metal tongues is completely worn out (see figure below). Replacements for damaged
Electronic Solar Switch handles are available from SMA.

Metal tongues

worn-out metal tongues