Power limitation – SMA CLUSTER CONTROLLER Installation User Manual

Page 54

Advertising
background image

Connection of a 24 V Signal Source with Digital Output Signals

Figure 19: Connection of a 24 V signal source with digital output signals (example)

6.12.2.2 Connecting a Signal Source to a Digital Input for Active Power

Limitation

Digital signals for active power limitation can be transmitted to up to four pin groups at terminal X4
on the Cluster Controller. A ripple control receiver or a remote terminal unit can be used as a digital
signal source, for example.

Additionally required material (not included in the scope of delivery):

☐ Up to four digital signal sources
☐ Connection cable (see Section 6.3 "Cable Requirements", page 30)

Requirements:

☐ The signal source must be technically suitable for connection to the digital inputs (see

Section 9, page 84).

☐ The connection cable must be prepared for connection to the multipole plug (see Section 6.5,

page 33).

6 Connection and Commissioning

SMA Solar Technology AG / SMA America, LLC

Installation Manual

ClusterController-IA-en-14