1 prepare cables for connecting to rails – SMA SC 500U Installation User Manual
Page 48
Advertising

SMA Solar Technology AG
48
SC500U-IUS093411
Installation Guide
Connecting 2 Cables to a Rail
Figure to the right: Layout for connecting a cable lug to
the rail in the Control Cabinet.
8.4.1 Prepare Cables for Connecting to Rails
1. Before connecting the cables, clean the contact surfaces.
2. Use only the non-woven abrasive delivered with the Sunny Central. Do not clean the surfaces
with sandpaper.
3. Do not touch the contact surfaces after they have been cleaned.
☑ The cable/s are connected to the rail.
A
Screw head
B
Lock washer
C
Cable lug
D
Rail
E
Nut
NOTICE
When transporting and storing the Sunny Central, oxide layers may form on the contact
surfaces of the cable connection.
Yield loss due to poor electrical conductivity.
E
B
C
D
C
B
A
Advertising