Maximum
number of
disconnect
blades
8
8
8
6
Possible sizes
of LV/HRC
fuses
80 A / 100 A /
125 A / 160 A
80 A / 100 A /
125 A / 160 A
80 A / 100 A /
125 A / 160 A
80 A / 100 A /
125 A / 160 A /
200 A
Maximum
operating
current per
measuring
input with
80 A LV/HRC
fuse
52 A
52 A
52 A
52 A
Maximum
operating
current per
measuring
input with
100 A
LV/HRC fuse
65 A
65 A
65 A
65 A
Maximum
operating
current per
measuring
input with
125 A
LV/HRC fuse
81 A
81 A
81 A
81 A
Maximum
operating
current per
measuring
input with
160 A
LV/HRC fuse
104 A
104 A
104 A
104 A