SMA SMB User Manual
Page 31

SMA Solar Technology AG
10 Technical Data
Installation Manual
SMB-IA-en-10
31
Maximum
operating
current per
measuring
input with
200 A
LV/HRC fuse
‒
‒
‒
130 A
DC input
Screws for fuse
holders
M 10
M 10
M 10
M 10
Torque
30 Nm … 35 Nm 30 Nm … 35 Nm 30 Nm … 35 Nm 30 Nm … 35 Nm
Cable gland
8 x M40
‒
‒
‒
Sealing range
14 mm … 28 mm
‒
‒
‒
Seal insert pre-
mounted
14 mm … 18 mm
‒
‒
‒
Seal insert
included in
scope of
delivery
7 mm …
20.5 mm /
20 mm … 25 mm /
24 mm … 28 mm
‒
‒
‒
Maximum
cable cross-
section
240 mm
2
240 mm
2
240 mm
2
240 mm
2
DC output
Diameter of
through-hole in
busbar
3 x 13 mm
2 x 3 x 13 mm
2 x 2 x 2 x 13 mm 2 x 2 x 2 x 13 mm
Maximum
cross-section
of standard
terminal lug
240 mm
2
240 mm
2
240 mm
2
240 mm
2
Screws
included in
scope of
delivery
3 x M12 /
2 x M12*
2 x 3 x M12
2 x 2 x 2 x M12
2 x 2 x 2 x M12
Torque
74 Nm
74 Nm
74 Nm
74 Nm
Sunny Main Box Sunny Main Box
Cabinet
Sunny Main Box
Cabinet
Sunny Main Box
Cabinet
Option
8 inputs
2 x 8 inputs
2 x 2 x 4 inputs
2 x 2 x 3 inputs