SMA SMC 4600A Installation User Manual
Page 29
Advertising

SMA Solar Technology AG
Electrical Connection
Installation Manual
SMC46-60A11-IA-en-81
29
4. Push the screw connection to the thread and fasten to a torque of 2 Nm.
☑ The DC connectors are assembled and can now be connected to the inverter as described in
Section 5.4.4 "Connecting the PV Array (DC)" (page 31).
☑ If the stranded wires are not visible in the
chamber, the cable is not correctly
positioned.
• Release the clamping bracket. To do so,
insert a screwdriver into the clamping
bracket to lever it open (blade width:
3.5 mm).
• Remove the cable and go back to step 1.
Result