3 windy boy protection box 600, Windy boy protection box 600 – SMA WBP-Box User Manual
Page 24
Advertising
10 Technical Data
SMA Solar Technology AG
24
WBP-Box-IEN103320
Installation Guide
10.3 Windy Boy Protection Box 600
Small wind turbine system connection
Wind power inverter connection
Load resistor connection
General data
* According to IEC 60529
Quantity
1 x 3-phase
Voltage
3 x 0 V … 500 V
Current
3 x 0 A … 11.5 A
Frequency
0 Hz … 400 Hz
Nominal power
2 kW … 7 kW
Maximum number
2
Voltage limitation
600 V
Total power
7 kW
Quantity
1
Nominal voltage
600 V
Continuous power
7 kW
Width x height x depth
280 mm x 220 mm x 130 mm
Weight
5 kg
Rectifier
Integrated
Peak efficiency
99.95 %
Operating temperature range
− 25 °C … 65 °C
Protection rating *
IP54
Load loss at continuous power
30 W