SMA Solar Technology AG

5  Mounting

Installation Manual

WB3-5TL-21-IA-en-10

23

5 Mounting

5.1 Selecting the Mounting Location

Requirements for the mounting location:

☐ The mounting location must be inaccessible to children.
☐ A solid foundation must be available for mounting, e.g. concrete or masonry. When mounted

on plasterboard or similar materials in a living area, the inverter will develop audible vibrations
during operation, which could be considered disturbing.

☐ The mounting location must be suitable for the weight and dimensions of the inverter

(see Section 13 "Technical Data", page 77).

☐ The mounting location must be easily and safely accessible at all times without the use of

additional aids being necessary, e.g., scaffolding or lifting platforms. Non-fulfillment of these
criteria may restrict servicing.

☐ The mounting location must not be exposed to direct solar irradiation. Direct solar irradiation

can overheat the inverter. As a result, the inverter reduces its power output.

☐ Climatic conditions must be met (see Section 13 "Technical Data", page 77).
☐ The ambient temperature must be below 40°C to ensure the optimal operation of the inverter.

Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.

• Do not mount the inverter on flammable construction materials.
• Do not mount the inverter in areas where highly flammable materials are stored.
• Do not mount the inverter in a potentially explosive atmosphere.