9  Disconnecting the Inverter from Voltage Sources

Installation Manual

WB3-5TL-21-IA-en-10

55

9. Unlock and disconnect all DC connectors. To do

this, insert a screwdriver into one of the side slots
(blade width: 3.5 mm) and pull the DC connectors
straight down. Do NOT PULL ON THE CABLE
while doing this.

10. Ensure that no voltage is present on the DC inputs

using a suitable measuring device.

11. Ensure that no voltage is present on the AC

connecting terminal plate between L and N using a
suitable measuring device. Insert the test probe
(maximum diameter: 2 mm) in each round opening
of the terminal.