View Status Options

20

5.1

View Cable Status

The Cable Status screens display the overall status of the cable con-

nected to each of the two zones monitored by the Liqui-tect panel, as

well as the length of the cable being monitored and the amount of cur-

rent present in each cable.
To view the status of the cable:

• From the Main Menu, use the arrows

↑↓

to

choose View Status, as

shown at right, and then press Enter

.

• From the View Status Menu, use the arrows

↑↓

to

choose View

Cable Status and press Enter

.

5.1.1 Cable Status Screens

Each Cable Status screen displays the zone name (

ZN1

or

ZN2

) and its

label (for example,

ZONE 1

or

ZONE 2

) at the top.

Viewing Additional Screens

There are four Cable Status screens—two for each zone.

• To view additional screens, use the arrows

↑↓

.

• To return to the previous screen, press the ESC key.
• When finished viewing the last screen, press Enter

.

Overall Condition

The first screen for each zone shows:

• the zone name (

ZN1

or

ZN2

) and its label (for example,

ZONE 1

or

ZONE 2

)

• the current overall condition of the cable (for example,

NORMAL

)

The cable conditions tracked by the Liqui-tect panel appear in Table 5.

Cable Length & Current Value

The second screen for each zone shows:

• the zone name (

ZN1

or

ZN2

) and its label (for example,

ZONE 1

or

ZONE 2

)

• the length of cable being monitored (for example,

1000FT

)—this value may change dynamically by

up to 0.5% as the panel is continuously calculating the distance of the connected cable

• the current reading (

0UA

, where UA represents µA or microAmps)

Table 5

Overall cable conditions

SOURCE

Cable

CONDITIONS

RECORDED

NORMAL

CABLE BREAK

LEAK DETECTED (& location, e.g., LEAK @ 99 FT)

CONTAMINATED (& location, e.g., CONTAM @ 44 FT)

NOT INSTALLED

Main Menu

> VIEW STATUS

SYSTEM AND CONTROL

↑↓

=NEXT

=SELECT

View Status Menu

> VIEW CABLE STATUS

VIEW ALARM HISTORY
VIEW ZONE TREND

↑↓

=NEXT

=SELECT

Overall Condition (ZN1)

STATUS ZN1 ZONE 1

NORMAL

↑↓

=NEXT

Length & Current (ZN1)

STATUS ZN1 ZONE 1

LENGTH:

1000FT

CURRENT: 0UA

↑↓

=NEXT

=DONE

Overall Condition (ZN2)

STATUS ZN2 ZONE 2

NORMAL

↑↓

=NEXT

Length & Current (ZN2)

STATUS ZN2 ZONE 2

LENGTH:

3500FT

CURRENT: 0UA

↑↓

=NEXT

=DONE

Advertising