4 controller board overview, Table 1 controller board components, Controller board overview – Emerson Liqui-tect MC68HC16Z1 User Manual

Page 8: Controller board components

Advertising
background image

Introduction

4

1.4

Controller Board Overview

The Liqui-tect panel’s controller board, as shown below, has connectors for two digital outputs for leak

detection alarms, two digital outputs for cable break alarms, two inputs for leak detection cables and

two analog outputs for connecting to a building management system. The board comes complete with

light-emitting diodes (LEDs) to display the status of monitored zones, power connections and other

features necessary to monitor and protect your operation.

Table 1

Controller board components

Item

Description

More Information

A-Power On/Off LED

Indicates when power is supplied to the panel.

2.4:

Connect Power to the Liqui-tect Panel

1.5:

LED Indicators

B-DIP switch 1

DIP switch used for resetting password to default

and disabling the audible alarm.

3.5:

Disable the Audible Horn

6.8.1: Change Password

C-DIP switch 2

Not used.

N/A

D-Audible horn

Provides audible notification when an alarm occurs.

3.5:

Disable the Audible Horn

E-Digital alarm

outputs (Zone 1)

and

G-Digital alarm

outputs (Zone 2)

The Cable Break output connection is a two-state

point (ON/OFF, energized/de-energized). When the

cable is broken or becomes contaminated, an alarm

is created and the contact is energized.
The Leak Detected output connection is a two-state

point (ON/OFF, energized/de-energized). When

water is detected, an alarm is created and the

contact is energized.
Each output can be used to connect to a secondary

warning device such as a horn, light or building

management system.

3.0:

Connections and Configuration

3.2:

Connecting Alarm Outputs

5.1:

View Cable Status

6.5:

Setup System - Setup Alarm Outputs

F-Alarm output

LEDs (Zones 1&2)

Indicates the status of the alarm outputs.

1.5:

LED Indicators

G-Digital alarm

outputs (Zone 2)

(See description and references for E-Digital alarm outputs (Zone 1) above)

ON

TB3

C28

R16

R17

R18

DS3

DS4

DS5

K1

K2

K4

K5

TX RX

A

1

SW2

SW1

R4

O N

2

3

4

5

6

7

8

1

O N

2

R1

R40

R44

DS7

DS8

R38

C26

C27

C40

C33

U15

U23

C32

U22

C46

U29

U24

U24

U16

DS1

Pwr On

24V Pow

LCD Interlface

3

4

5

6

7

8

Fault

LEDO

DS6

Reset

A-Power On/Off

LED

B-DIP

switch 1

C-DIP

switch 2

D-Audible

horn

E-Digital alarm

outputs (Zone 1)

F-Alarm output

LEDs (Zones 1&2)

G-Digital alarm

outputs (Zone 2)
H-Status LEDs

M-RS232

LEDs

I-4/20mA output

(Zone 2)

J-4/20mA output

(Zone 1)

K-Input cable

connector (Zone 2)

L-Input cable

connector (Zone 1)

N-RS232

connector

O-SiteScan

Web connector

P-SiteScan

Web LEDs

Q-RS485

LEDs

R-RS485

connector

(not used)

V-LCD

connector

W-LCD contrast

adjustment

X-Reset

switch

Y-24VAC power

connector

Z-Transformer

Module

S-Power

receptacle

T-Power On/

Off switch

U-24VAC

connector