Grid Frequency Range
Every voltage and frequency range is adjustable and password protected.
Frequency Range
System Condition
XP100U-H2/ XP100U-H4
XP83U-H6/XP90U-H6/XP100U-H6
Trip Time
f<rated-3.0
Grid Minimum Frequency
f<57.0
10 cycles
f<rated-0.7
Grid Under Frequency
f<59.3
10 cycles
rated-0.7≤f≤rated+0.5
Normal Operation
59.3≤f≤60.5
-
f>rated+0.5
Grid Over Frequency
f>60.5
10 cycles