Magnum Energy GFCI Outlet (MS-GFCI) User Manual

Ms-gfci instruction sheet, 0 introduction, 0 installation

Advertising
background image

MS-GFCI Instruction Sheet

Part Number: 64-0057 Rev B

1

Magnum Energy, Inc.

2211 West Casino Road

Everett, WA USA 98204

www.magnumenergy.com

1.0 Introduction

The MS-GFCI accessory allows a GFCI (Ground Fault Circuit Interrupter) recep-
tacle to be installed directly on a Magnum inverter. This accessory includes a
duplex GFCI 20-amp rated outlet that can be easily wired and attached to the
right side of the inverter. The GFCI outlet quickly stops the flow of electricity in
the event a ground fault occurs on the device that is plugged into the inverter.

A GFCI receptacle does NOT protect against circuit overloads, short circuits,
or shocks; therefore, the MS-GFCI accessory can only be safely installed
on a Magnum inverter that includes output branch-rated circuit protection.
This integral output circuit protection is only available on Magnum Energy’s
MS2000-20B or MS2012-20B inverter/charger models.

2.0 Installation

The following pertains to attaching the GFCI accessory to the MS2000-20B
or MS2012-20B inverter/charger models.

WARNING: Installing the MS-GFCI accessory on an inverter with-
out integral output circuit protection (i.e., not a -20B model) may
cause the wires to overheat and cause a fi re.

WARNING: Installations should be performed by personnel that
understand basic wiring principles and techniques, can interpret
wiring diagrams, have circuit wiring experience, and are prepared
to take a few minutes to test their work to ensure the GFCI recep-
tacle is wired correctly.

WARNING: Before proceeding — to prevent accidental shock — do
not
touch any parts inside the inverter until all sources of power to
the inverter are de-energized (i.e., breakers open, fuses removed).
This includes all DC power (i.e., batteries, solar, wind or hydro)
and AC power (utility power or AC generator). Use a voltmeter to
ensure all power has been removed.

2.1 Tools Required

To install the GFCI outlet panel you will need:

•

Flat blade screwdriver

•

Phillips screwdriver

•

AC voltmeter

•

Test lamp (rated at 120 VAC)

2.2 Attaching the GFCI to the Inverter

To wire the GFCI outlet to the inverter, follow these steps:

1. Remove the two Phillips screws (#8-32) that hold the existing AC access

panel to the inverter (retain for attaching the GFCI outlet panel).

2. Connect the voltmeter between the AC HOT 1 OUT and the AC NEUT OUT

terminals/wires. Ensure there is no voltage present on any terminals/
wires.

3. Connect the GFCI outlet’s 3 pre-stripped wires as follows (refer to

Figure 1 for MS2012-20B models, or Figure 2 for MS2000-20B models):