CAC Cassette Evaporator

S2C REFRIGERANT CHARGE TABLE

Condenser

Evaporator Pairing

Line Chg/Ft

Factory Charge

Ref.

S2CA99

CACA12

.25 oz.

28 oz./ 28 oz.

R-22

S2CA22

CACA12

.25 oz.

33 oz./ 33 oz.

R-22

S2CA92

CACA12+CACA12

.25 oz.

28 oz./ 33 oz.

R-22

S1C REFRIGERANT CHARGE TABLE

Condenser

Evaporator Pairing

Line Chg/Ft

Factory Charge

Ref.

S1CA9

CACA12

.25 oz.

37 oz.

R-22

S1CA2

CACA12

.25 oz.

40 oz.

R-22

S1CA8

CACA24

.56 oz.

51 oz.

R-22

S1CA4

CACA24

.56 oz.

65 oz.

R-22

S1CA3

CACA36

.56 oz.

72 oz.

R-22

S1CA6

CACA36

.56 oz.

90 oz.

R-22

8. Charge to proper weight, charge based on

your feet of interconnect (see below).

NOTE: Charging should be done with a

dial-a-charge or weighed in with a scale.

TOP DISCHARGE REFRIGERANT CHARGE CHART

Circuit Capacity

Line Chg/Ft

Factory Charge

Ref.

09

.25 oz.

28 oz.

R-22

12

.25 oz.

30 oz.

R-22

18

.56 oz.

48 oz.

R-22

24

.56 oz.

60 oz.

R-22

IMPORTANT NOTES:

I. To find the charge adjustment and system charge for any evaporator and tubing length:

Line Adjustment = (Line Chg/Ft) x Line Length

System Total = Factory Charge + Line Adjustment

2. Round to the nearest ounce and allow for gauges and hoses.

3. Use R22 refrigerant.

REFRIGERANT PROCESSING

Refrigerant

Refer to Refrigerant

Charge Table for

specified line charge.