Installation – Enviro 2100 User Manual

Page 12

Advertising
background image

Installation

I

NSTALLATION

:

A non-combustible floor protector is required under all freestanding units, refer to “Clearances To

Combustibles - Freestanding”. When venting into a masonry chimney the floor protector must be installed

directly below the chimney vent and 2” (50.8 mm) on either side of the chimney vent.

Vent the stove into a clean, lined, approved masonry chimney in good condition, conforming to local

building codes or a listed 6” (150 mm) factory built chimney suitable for use with solid fuels and conforming

to, ULC-S629 in CANADA or UL-103HT in the U.S.A.. Connect the stove to this chimney with a short and

straight 6” (150 mm), 25 gauge or heavier, single wall black or blued steel smoke pipe. Connection to all

masonry chimneys must be a metal or masonry thimble cemented in place. All smoke pipes must slope

upwards, all connections must be tight and secured with three sheet metal screws equally spaced. The

smoke pipe length should not exceed 40% of the chimney height above the stove.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.

���������

�����

��������

����� ������ �� �����

���������

��������

���

������� ��� ����������

������� ���� �� �����

�� ����

����� ��

�������

��� �������� �� ������ ���� �� ����� ����� ���� �

�� ���� ��� ��������� ����� ����� ���� ��� �������

��������� �� ��� ��� �� ��� ��������

������� �������� ��������������� �������

�� ������ ��� ���� �� �������� �� ������

������ �� ������ ������ ����

������� ����������

NOTE: In installations where there is constant or frequent high winds, install a flue damper to reduce

the effect that high winds have on increasing the draft. A significant increase in draft due to high winds

may cause your unit to overfire, which could be hazardous and will void the warranty.

12

Advertising