Using the sizing calculation – Eaton Electrical Cutler Hammer MN05001002E User Manual

Page 23

Advertising
background image

Intelligent Technologies QCPort System Install Manual

November 2005

MN05001002E

For more information visit

www.eatonelectrical.com

Page

23

Using the Sizing Calculation

The following examples use the sizing calculation to determine if the power supply is
placed correctly in the system and if the power supply is large enough for the application.

Example 1 End Connected Power Supply

1. Sum up all the currents (QCPort Interconnect system)

=0.1 + 1.1 + 0.3 = 1.5A (too much for Interconnect)

The supply will have to be relocated.

Example 2 End Connected Power Supply

1. Sum up the currents (QCPort Interconnect system)

=0.1 + 0.4 + 0.3 = 0.8 A (OK since 10 feet allows 1.0A)

2. Find the voltages for each node using the equation for Long Run.

SUM {[(L

n

x (0.105)) + (N

t

x (0.005))] x I

n

} <= 4.65V

Device 1 [(20 x (0.105)) + (1 x (0.005))] x 0.1 = 0.21V

Device 2 [(30 x (0.105))+ (2 x (0.005))] x 0.4 = 1.26V

Device 3 [(40 x (0.105)) + (3 x (0.005))] x 0.3 = 1.26V

3. Add each Devices voltage together to find the total voltage.

0.21 + 1.26 + 1.26 = 2.73V (OK)

Results

Since the total voltage does not exceed 4.65V, the system will operate properly.