Eaton Electrical Cutler Hammer MN05001002E User Manual

Page 24

Advertising
background image

Intelligent Technologies QCPort System Install Manual

November 2005

MN05001002E

For more information visit

www.eatonelectrical.com

Page

24

Example 3 Middle Connected Power Supply

2. Sum up the currents per section

Section 1 (QCPort Interconnect) = 0.2 + 0.3 + 0.1 = 0.6 A (OK)

Section 2 (Backplane) = 1.0 + 2.0 = 3.0 A (OK)

Find the voltages for each device using the equation for Long Run.

SUM {[(L

n

x (0.105)) + (N

t

x (0.005))] x I

n

} <= 4.65V

Device 1 [(9 x (0.105)) + (3 x (0.005))] x 0.2 = 0.19V

Device 2 [(6 x (0.105))+ (2 x (0.005))] x 0.3 = 0.19V

Device 3 [(3 x (0.105)) + (1 x (0.005))] x 0.1 = 0.03V

Device 4 [(0 x (0.105)) + (1 x (0.005))] x 1.0 = 0.00V

Device 5 [(0 x (0.105)) + (2 x (0.005))] x 2.0 = 0.02V

Add each Devices voltage together to find the total voltage per section.

Section 1 – 0.19+0.19+0.03 = 0.41V (OK)

Section 2 – 0.00+0.02 = 0.02V (OK)

Results

Since the total voltage does not exceed 4.65V in either section, the system will operate
properly.

T

D3

.1A

PS

D4

1 A

D2

.3 A

D5

2 A

3 foot

3 foot

3 foot

0 foot

T

D1

.2 A

0 foot

Section 1

Section 2

3 foot