Emerson Process Management ControlWave EFM 3808 User Manual

Page 91

Advertising
background image

CI-ControlWave EFM

Installation & Operation / 2-39

Figure 2-25 - RTD Probe Installation/Removal Diagram

2.3.6 21V Power Supply Option


21V Power Supplies are mainly used in conjunction with Temperature and Pressure
Transmitters which require a higher than +12V but lower than +21.4V (

±.8V) input supply

to operate (such as Series 3508 Transmitters).

Figure 2-26 - 21V Power Supply Board


21V Power Supply Boards contain two terminal blocks that accommodate power con-
nections between the ControlWave EFM and remote transmitters. TB1 is a three-position
terminal block that provides input power connection from the Power Distribution Board.
Four-position Terminal Block (TB2) provides +21V power and ground to external devices
such as Series 3508 Transmitters.