Index – Emerson 90 SERIES 1F95-391 User Manual

Page 39

Advertising
background image

37

INDEX

SYMPTOM

Thermostat Setting and
Thermostat Thermometer
Disagree

Thermostat Does Not Follow
Program

Blank Display and/or Keypad
Not Responding

POSSIBLE CAUSE

1. Thermostat thermometer setting
requires adjustment.

1. AM or PM set incorrectly in
program.
2.AM or PM set incorrectly on the
clock.
3. Voltage spike or static discharge.

1. Voltage spike or static discharge.

CORRECTIVE ACTION

The thermostat can be adjusted +/- 5°F. See the
Temperature Display Adjustment in the Operating
Manual under configuration.

Check current clock and program settings including
the AM or PM designations for each time period. If a
voltage spike or a static discharge occurs use the
Reset Operation listed above.

Check heat/cool system for proper operation. If a
voltage spike occurs, use the Reset Operation by
pressing FAN, TIME

BACK

, and the temperature

arrow at the same time.

Troubleshooting