3.1 OPERATING SPECIFICATIONS

Function: Provides four isolated 24Vdc power output terminal pairs to

power an RTU , a Transmitter and/or a number of non-isolated
I/O (associated with a particular ControlWave RTU.

Output Voltage : Electrically Isolated & Regulated 24Vdc

±5%, no load or full

load

Output Current:

0.2A maximum, power limited to 150% of Max. rated power

Supply Shutdown: Below +9Vdc or +19Vdc (Nominal) for 12V or 24V system

(respectively)


12V

System:

Max. ON Switchpoint = 8.8V

Max. OFF Switchpoint = 7.8V


24V

System:

Max. ON Switchpoint = 19.7V

Max. OFF Switchpoint = 17.4V

Input Voltage: +9 to +30 Vdc

Input Current: Supply Loading: 24V @ 0.2A

Vin @ +9V Iin Max. = .85A

Vin @ +12V Iin Max. = .58A

Vin @ +24 Iin Max. = .29A


Fusing: 2A Slow Blow (5x20 mm) Fuse for 12V/24V System

Electrical Isolation: 500Vdc (Transformer Coupled)

Surge Suppression: 500Vdc (MOV between 24V return and CHASSIS)
30V Transient Suppressor across VIN(9-30V)/GND, 24V/24V

Return – meets ANSI/IEEE C37.90-1978


Terminations:

Fixed, Max. wire size is 16 guage

3.2 ENVIRONMENTAL SPECIFICATIONS

Temperature:

Operating Range: -40° to +85°C (-40° to 185°F)

Storage Range: -40°to +85°C (-40°to 185°F)

Relative Humidity:

15% to 95% (Non-condensing)

Advertising