PIP-ControlWaveLS

Page - 11

Vibration: 1g for 10-500 Hz on any axis per SAMA PMC-31-1 without

damage or impairment.

.5g for 150-2000Hz


RFI Susceptibility:

10V/meter – 80MHz to 1000MHz

3.3 CONNECTORS

3.3.1 Terminal Block TB1


3-Pin Terminal Block TB1 accommodates input power from the bulk DC source. TB1 could
act as a power pass-through interface to an RTU (in lieu of connector TB3) (see Table 1).

3.3.2 Terminal Block TB3


3-Pin Terminal Block TB3 typically accommodates pass-through power to the associated
ControlWave RTU but could act as the Loop Supply input power interface (in lieu of
connector TB1) (see Table 1).

3.3.3 Terminal Block TB2


8-Pin Terminal Block TB2 accommodates distribution (four pairs of wiring terminals) of
regulated +24Vdc loop power (see Table 2).

3.4 PART NUMBERS


400095-01-7 Snap Track Mount
721708-01-3 Panel Mount
721708-02-1 35mm DIN Rail Mount

3.5 DIMINSIONS


Dimensions are provided in Figure 6.