SOFTWARE INSTALLATION AND SET-UP PROCEDURE

LBI-39101

29

Set-Up And Troubleshooting maintenance manual,
LBI-38938. A "

User Profile

Successfully Written...

" message must

be received before continuing.

System Manager Database Uploads

System Manager databases contain all system

information for all defined entities (units, groups, sites).
These databases can be downloaded to the console by
requesting database uploads from the CEC/IMC Manager.
Since this data is broadcast to all consoles in the CEC/IMC
system, if possible, all consoles should be on-line when this
upload occurs. This avoids having to repeat the process for
other consoles at a later time.

1. From the CEC/IMC Manager's "

CEC/IMC MOM

Options

" main menu, select the "

System

Manager Data

" option. This will display the

System Manager data menu.

2. Select

"

Upload From System Manager

".

3. From the "

SYSTEM MANAGER UPLOAD

STATUS

" screen, select <F1> then <F8> for a full

unit upload. After the upload is complete, exit the
unit upload screen by pressing <Esc>.

4. From the "

SYSTEM MANAGER UPLOAD

STATUS

" screen, select <F2> then <F8> for a full

group upload. After the upload is complete, exit the
group upload screen by pressing <Esc>.

5. From the "

SYSTEM MANAGER UPLOAD

STATUS

" screen, select <F6> then <F8> for a full

site upload. After the upload is complete, exit the
site upload screen by pressing <Esc>.

6. From the "

System Manager Data

" menu,

select the "

Upload From MOM PC

" option.

7. From the "

MOM PC BASED SYSTEM MANAGER

UPLOAD STATUS

" screen, select <F3> then <F8>

for a full conventional channel upload. After the
upload is complete, exit the conventional upload
screen by pressing <Esc>.

8. From the "

MOM PC BASED SYSTEM MANAGER

UPLOAD STATUS

" screen, select <F5> then <F8>

for a full console upload. After the upload is
complete, exit the console upload screen by
pressing <Esc>.

System Manager database uploads must be
accomplished before sending console privilege
lists.

Console Privilege Lists

Each console must be sent its privilege list from the

CEC/IMC Manager as follows:

1. From the CEC/IMC Manager's "

CEC/IMC MOM

Options

" main menu, select the "

Console

Configuration

" option. This will display the

console configuration menu.

2. From this menu, select the "

Console

Privilege List

" option.

3. From the "

CONSOLE PRIVILEGE LIST

UPLOAD

" screen, enter the number of the console

(1 - 32).

4. Select <F7> to send the privilege list data to the

console.

Saving Database Information

At the C3 Maestro console, the following database

information is saved automatically to the PC's hard disk
drive after the last record is received. No user action is
required:

User Profiles

Hardware Configurations

The following data is not saved automatically, but on

demand or by prompt:

System Manager Upload Data

CEC/IMC Manager Upload Data

Module Set-Ups

Upload data should be saved after it is transferred to the

console's PC. Modules set-ups should also be saved after
changes are made to the modules. Saving prevents
configuration problems if the PC's power is cycled or if it is
rebooted. To save upload data and module set-ups, press
<F10> on either keyboard. This will save the data to the
PC's hard disk.

CEC/IMC AUXILIARY I/O

A C3 Maestro console may be utilized to monitor and

control CEC/IMC auxiliary I/O (input/output) events.
CEC/IMC firmware/software version 4.x and earlier
provides 30 total auxiliary I/O events and version 5.x and
later provides 255 total auxiliary I/O events.

At the console, no auxiliary I/O-related configurations

are necessary; all auxiliary I/O configurations are
accomplished at the CEC/IMC Manager. Basically, these
configurations include, on a per auxiliary I/O event basis
(non-inclusive listing):

NOTE