ENVISION SERIES AIR HANDLER INSTALLATION MANUAL

Air Handler Sizing Selection

The Envision Air Handlers are designed for R410a refrigerant and should be matched with Envision Split series compressor

section according to the table below.

General Installation Information

Moving and Storage

If the equipment is not needed for immediate installation it

should be left in its shipping carton and stored in a clean,

dry area. Units must only be stored or moved in the normal

“up” orientation.

Unit Location

Locate the unit in an indoor area that allows for easy re-

moval of the filter and access panels (the air handler units

are not approved for outdoor installation). Location should

have enough space for service personnel to perform main-

tenance or repair. Provide sufficient room to make refriger-

ant, electrical and duct connections. If the unit is located

in a confined space, such as a closet, provisions must be

made for return air to freely enter the space by means of a

louvered door, etc. The air handler section may be installed

on any level surface strong enough to support its weight.

When installed in a closet or on a stand, it should be

mounted on vibration absorbing material slightly larger than

the base to minimize vibration transmission to the building

structure.

When installed in an attic or above a drop ceiling, the instal-

lation must conform to all local codes. If the unit is sus-

pended and installed in the horizontal position, the entire

length of the unit should be supported. If the application

requires the air handler to be installed on the attic floor

then the unit should be set in a full size secondary drain

pan. In this case the secondary drain pan should be set on

top of a vibration absorbing mesh. The secondary drain

pan is usually placed on a plywood base. A secondary drain

pan should be used when equipment is installed over a

finished living area to provide protection from water dam-

age in case of plugging of the air handler primary drain line.

The secondary drain line should terminate somewhere that

is easily visible by the homeowner. Be certain to show the

homeowner the termination location of the secondary drain

line and to explain its purpose.

Duct System

The duct system should be sized to handle the design air-

flow quietly and efficiently. To maximize sound attenuation

of the unit blower, the supply and return plenums should

include an internal duct liner of fiberglass or constructed

of ductboard for the first few feet. On systems employing

a metal duct system, canvas connectors should be used

between the unit and the ductwork. If air noise or exces-

sive airflow is a problem, the blower speed can be changed.

Application of the unit to un-insulated metal ductwork in an

unconditioned space will cause poor unit performance and

allow condensation to form on the duct and possibly cause

damage to the structure.

If the unit is connected to existing ductwork, check the duct

system to ensure that it has the capacity to accommodate

the air required for the unit application. If the duct is too

small, as in the replacement of heating only systems, larger

ductwork should be installed. All existing ductwork should

be checked for leaks and repaired as necessary.

Air Handler

Indoor Split Model

(Single)

Indoor Split Model

(Dual Capacity)

Outdoor Split Model

(Dual Capacity)

Airfl ow(CFM)

Electric Heat (kW)

NAH022A***1R

NSZ022

-

800

5

NAH026A***1R

-

NDZ026

NDS026

925

5

NAH030A***1R

NSZ030

-

-

980

5, 10

NAH036A***1R

NSZ036

-

-

1225

5, 10

NAH036A***1R

-

NDZ038

NDS038

1225

5, 10

NAH042A***1R

NSZ042

-

-

1425

10, 15

NAH048A***1R

NSZ048

-

-

1625

10, 15

NAH048A***1R

-

NDZ049

NDS049

1625

10, 15

NAH060A***1R

NSZ060

-

-

1760

10, 15, 20

NAH060A***1R

-

NDZ064

NDS064

1760

10, 15, 20

NAH060A***1R

NSZ070

-

-

1760

10, 15, 20

NAH060A***1R

-

NDZ072

NDS072

1760

10, 15, 20