Installation – MCZ Ego 2.0 AIR User Manual

Page 16

Advertising
background image

A

B

B

A

C

MIN.1,5 m

MIN.1,5 m

MIN.1,5 m

MIN.0,3 m

14

2-INSTALLATION

EXTERNAL AIR INLET

It is mandatory to provide an adequate external air intake that supplies the combustion air required for the product to work properly. The

flow of air between the outside and the installation room may be direct, through an inlet in an external wall of the room; or indirect, via

air intake from adjoining rooms and connecting permanently with the installation room (see Figure 9 b). Adjoining areas may not include

sleeping areas, garages or general areas with a fire hazard. During installation one must check the minimum clearances required for air

intake from outside. Take into account the presence of doors and windows that could interfere with the proper flow of air to the stove (see

diagram below).

The air intake must have a minimum total net area of 80 cm2: the surface must be increased accordingly if within the room there are other

active generators (for example: electric fan for stale air extraction, kitchen hood, other stoves, etc...), which could cause cause depression

in the room. One must verify that, with all the equipment on, the pressure drop between the room and the outside does not exceed a value

of 4 Pa. If necessary increase the intake section of the air inlet, which must be made at floor level and always protected with a bird-proof

outer protection grid and in such a way that it cannot be obstructed by any object.

It is possible to connect the air required for

combustion directly to the outside air inlet,

with a pipe of at least Ø50mm, with maximum

length of 3linear metres; each pipe bend shall be

considered equivalent to a linear metre. To attach

the pipe see the back of the stove.

For stoves installed in studio flats, bedrooms and

bathrooms (where allowed), it is mandatory to

connect the combustion air outside. In particular

for sealed stoves the connection must be sealed

in order not to compromise the overall sealed

characteristic of the system.

FIGURE 9 A - DIRECTLY FROM OUTSIDE

FIGURE 10

FIGURE 9 B - INDIRECTLY FROM THE ADJACENT ROOM

A=AIR INLET

B=ROOM TO BE VENTILATED

C=INCREASE OF THE GAP UNDER THE DOOR

Advertising