2-INSTALLATION

DISTANCE (metres)

The air inlet must be at a distance of:

1.5 m

UNDER

Windows, doors, smoke outlets, cavities, ....

1.5 m

HORIZONTALLY

Windows, doors, smoke outlets, cavities, ....

0.3 m

ABOVE

Windows, doors, smoke outlets, cavities, ....

1.5 m

AWAY

from smoke outlet

CONNECTION TO FLUE

The connection between the flue and the appliance must be via a smoke duct that conforms with EN 1856-2. The connecting section

must extend no more than 4 m horizontally, with a maximum incline of 3% and containing a maximum of 3 90% bends (accessible for

inspection - do not count the T joint at the appliance outlet).

The diameter of the smoke duct must be equal to or greater than that of the appliance outlet (Ø 80 mm).

TYPE OF DEVICE

SMOKE DUCT

Minimum vertical length

1.5 metres

Maximum length

(with 1 accessible 90° bend)

6.5 metres

Maximum length

(with 3 accessible 90° bends)

4.5 metres

Maximum number of accessible 90° bends

3

Horizontal sections

(minimum incline 3%)

4 metres

Use a smoke duct according to the regulations in force in the country of installation and verify that it is compatible with the product and

installation characteristics. The temperature class of the smoke duct must exceed operating temperatures of the appliance.

It is prohibited to connect more than one appliance to the same smoke duct, or the discharge from overhead cowling. It is prohibited to

extract the products of combustion directly through the wall, whether into indoor spaces or outdoors.

Should there be flammable or heat-sensitive structures, the smoke duct must respect the safety distances specified in the data plate.

SUPPLEMENTARY ISTRUCTIONS ONLY FOR UK

FOR CONNECTION TO THE FLUE PIPE, NOT MORE THAN 150mm OF HORIZONTAL PIPE MUST BE USED AND NOT MORE THAN 4 x

45° bends MUST BE USED. I accordance with UK Building Regulations .

All exterior flue or flue used internaly above 1.8m should be twin wall insulated pipe installed in accordance with ADJ reference page 23

section 1.31 and 1.32 and 1.33 & Hetas regulations.

The external fluepipe must have internal dimensions of a minimum of 150mm, and maximum 180mm.

Check with suitable instruments that there is a minimum draught of 5 Pa. on low fire and 10pa on high fire. The flue must

always run under negative pressure and a cold flue pull of – 2>3 pascals must be secured.