Thermostat location – Empire Comfort Systems DV-210-7SG User Manual

Page 10

Advertising
background image

Page 10

12433-5-0606

These heating thermostats are specially designed for use on self-

generating systems. They should never be used on line or low

voltage A.C. circuits.
Exterior Wall — The thermostat may be mounted on an exterior

wall above the heater if it is located in the same stud space as the

vent tubes and is a minimum of 6" (152mm) above the heater.
Interior Wall — The thermostat should be installed on an inside

wall away from the unit but in the same room.
Note: Use 16 gauge wire to prevent excessive loss of millivolts.
Proper operation depends on a good pilot flame. The flame must

cover the top of the thermopile. Cleaning of the pilot orifice and

burner may be required due to spiders.
System Check

A millivolt meter is required to check the system. The millivolt

readings should be:
• Across the thermopile terminals, 400-450 millivolts with ther-

mostat OFF.

• Across the thermopile terminals, 150-250 milllivolts with ther-

mostat ON.

• Across the thermostat wires at the valve, less than 30 millivolts

with thermostat ON.

• Across the thermostat wires at the thermostat, less than 5 mil-

livolts with thermostat ON. (Strong winds, dirty pilot and low

pressure will reduce readings.)

Piezo Pilot Ignitor Instructions

Depressing the piezo ignitor button completely causes a spark to

occur at the pilot. This is a substitute for a match which requires

opening the pilot hole cover.
To light the pilot, it is important that the electrode be 1/8" (3mm)

from the thermopile. The spark must occur at the point the burner

flame hits the thermopile. The end of the electrode will be red hot

with the pilot on.
On a new installation with air in the gas line, it is suggested that a

match be used. The match will light the pilot faster than the piezo

under this condition.

Figure 6

THERMOSTAT LOCATION