Model PD6060 Dual-Input Process Meter

Instruction Manual

60

Latching Relay (Lt-Clr)

Manual reset only after alarm condition has cleared

Condition

LED

Relay

Normal Off

Off

Alarm On

On

Ack (No effect)

On

On

Normal On

On

Ack Off

Off

In this application, the meter is set up for manual reset only after the
signal passes the reset point (alarm condition has cleared).
Acknowledging the alarm while it is still present has no effect on either
the LED or the relay. When the alarm is acknowledged after it returns to
the normal state, the LED and the relay go off. Notice that the LED
remains on, even after the meter returns to the normal condition. This is
because, for latching relays, the alarm LED reflects the status of the
relay, regardless of the alarm condition.

Acknowledging Relays

There are two ways to acknowledge relays programmed for manual
reset: via the programmable front panel function keys F1-F3 (Default:
F3 assigned to ACK) and remotely via a normally open pushbutton
wired across one of the digital inputs and the +5 V terminals on the
digital I/O modules (Default: DI-4 assigned to ACK). When the ACK
button or the assigned digital input is closed, all relays programmed for
manual reset are acknowledged.

+5

I1

I2

I3

I4

O1

O2

O3

O4

G

DO 1-4

GND

ACK

PDA1044 Digital I/O Module

1

2

3

4

5

6

7

8

9

10

DI 1-4

Figure 19. Acknowledge Relays w/Function Key or Digital Input