Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual

Page 56

Advertising
background image

56

U

SE

FUNCTION

DESCRIPTION

PREDEFINED

POSSIBLE CONFIGURATIONS

MODE

Battery test

Time interval for the

automatic battery test

40 hours

Disabled
1 ÷ 1000 in steps of 1 hour

Alarm threshold

for maximum

load

Selects the overload

user limit

Disabled

Disabled
0 ÷ 103 in steps of 1%

Display

brightness

Selects the level of

brightness of the LCD

Maximum

Minimum ÷ Maximum in 20 steps

Sound alarm

Selects the mode of

operation of the sound

alarm

Reduced

Normal
Reduced: does not sound for

momentary intervention of the bypass

ADVANCED FUNCTIONS

Input frequency

tolerance

Selects the permitted

range for the input

frequency for

switchover to bypass

and for output

synchronization

± 5%

± 0.25%
± 0.5%
± 0.75%
± 1 ÷ ±10 in steps of 1%

Bypass voltage

thresholds

Selects the permitted

voltage range for

switchover to bypass

Low: 180V
High: 264V

Low :

180 ÷ 200 in steps of 1V

High:

250 ÷ 264 in steps of 1V

Bypass voltage

thresholds for

ECO

Selects the permitted

voltage range for ECO

mode operation

Low: 200V
High: 253V

Low: 180 ÷ 220 in steps of 1V
High:

240 ÷ 264 in steps of 1V

Sensitivity of

intervention for

ECO mode

Selects the sensitivity

of intervention during

operation in ECO

mode

Normal

Low
Normal
High

Load power

supply in stand-

by

Power supply of the

load on bypass with

UPS switched of

(stand-by status)

Disabled

(load NOT

powered)

Disabled (not powered)
Enabled (powered)

Bypass operation

Selects the mode for

use of the bypass line

Normal

Normal
Disabled with input/output

synchronization

Disabled without input/output

synchronization