Echnical data table – Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual

Page 64

Advertising
background image

64

T

ECHNICAL DATA TABLE

MODELS

SDL 3300

SDL 4000

INPUT

Nominal voltage

[Vac]

220 / 230 / 240

Accepted range

[Vac]

0 ÷ 276

Voltage range ruling out battery intervention

[Vac]
[Vac]

[Vac]

Maximum: 276
Minimum: 164 ÷ 84

(from 100% to 50% of load in

linear mode)

Return to mains-powered operation: 180

Nominal frequency

[Hz]

50 - 60 +5

Maximum current

(1)

[A]

15

16

Nominal current

(2)

[A]

11

12

Power factor

0.98

Current distortion @ maximum load

7%

BYPASS

Accepted voltage range for switching

[Vac]

180 ÷ 264

Accepted frequency range for switching

Frequency selected ±5 %

Switching time

[msec]

Typical: 2 - Maximum: 4

BATTERY

Back-up time

[min / W]

6’ / 2300

5’30 / 2400

No. batteries / V / Ah

9 / 12 / 7 high rate discharge

Recharge time

[h]

4 ÷ 8

OUTPUT

Nominal voltage

(7)

[Vac]

220 / 230 / 240 ±1.5%

Static variation

(3)

1.5%

Dynamic variation

(4)

5% in 20 msec

Waveform

Sinusoidal

Voltage distortion @ linear load

3%

Voltage distortion @ distorting load

6%

Frequency

(5)

50 or 60 Hz selectable

Current crest factor

3 : 1

Nominal power

[VA]

3300

4000

Nominal power

[W]

2300

2400

MISCELLANEOUS

Leakage current to earth

[mA]

1

AC/AC efficiency

92%

Ambient temperature

(6)

[°C]

0 – 40

Humidity

< 90% non-condensing

Protections

Excessive battery discharge – Overcurrent – short-circuit

– Overvoltage – undervoltage - thermal

Hold-up time

[msec]

40

Noise level

< 40 dB(A) at 1 mt.

Dimensions H x L x D

[mm]

455 x 175 x 520

Weight

[Kg]

38

38

Advertising