19

LED DIAGNOSTIC INDICATORS

The control includes two LED’s that display diagnostic information.

LED1 is red and LED2 is green. These LED’s are used to display oper-

ational mode, fault information. A third LED, LED3 is used to display

status information. LED3 is yellow. These LED’s are used to display

operational mode, status, and fault information.

OPERATIONAL MODE DETECTION

The control can be used in a variety of applications including AC units

with multistage compressors. The control uses various inputs to deter-

mine the proper mode of operation.
The control senses the connections that are made to M, M1, and M2

terminals and determines the correct operational mode for the control.

This is done each time power to the control is cycled. Therefore, it is

important that no loads be attached to the M1 or M2 terminals of the

control for single-stage compressors, and no loads be attached to the

M1 terminal of the control for a scroll two-stage compressor.

OPERATIONAL MODE DISPLAY

The control will display its active operational mode using the onboard

LED’s when the TEST pins are connected while no thermostat signals

are energized. Table 3 "Operational Mode Display" describes the oper-

ational modes. The control will display the operational mode as long as

the TEST pins are shorted and no thermostat signals are energized.

When the TEST pin short is removed, the control will return to normal

LED displays.

STATUS CODE DISPLAY

The control also provides status codes using the LED’s. Status codes

indicate the state of the operation of the unit but do not represent a

fault. Tables 4 & 5 describes the LED displays during status codes. Sta-

tus codes will not be displayed when a fault code is present.

TABLE 2: TEST Input Functionality

Duration of

connection (seconds)

Control Behavior with no system

master signals present

Control behavior with system

master signals present

< 2

No response

No response

2 <

Display compressor type TS, Ultratech, or

single stage compressor, Ignore LPS

Bypass ASCD (Reduce timer to zero immediately).

If Y1 (thermostat or communication) is present and the

high-pressure switch is closed, contactors will be energized.

Clear soft lockout

Clear soft lockout

Clear hard lockout

Clear hard lockout

Reset TS anticipation mode counter

to zero for TS systems.

Reset TS anticipation mode counter

to zero for TS systems.

Reduce TS staging delays for TS

systems as described below.

Connection removed

Resume normal LED display

Connection not removed

Nothing more than previously explained

Do not connect any loads to the M1 or M2 terminals of the control
for single-stage compressors, and no loads should be attached to
the M1 terminal of the control for scroll two-stage compressor.
Incorrect system behavior could result.

TABLE 3: Operational Mode Display

Compressor Type

LED1 (Red)

LED2 (Green)

Single Stage Compressor

1 flash

---

TS Compressor

2 flashes

---

UltraTech Compressor

3 flashes

---

TABLE 4: Status Code Display

Description

Required Condition

LED1 (Red)

LED2 (Green)

No power to control

No power to control

OFF

OFF

First-stage compressor operation – TS or UltraTech

TS – M & M1 energized,

UltraTech – M energized,

Single Stage - NA

OFF

ON

Second-stage compressor operation - TS, UltraTech, or

Single Stage

TS and UltraTech – M & M2 energized,

Single Stage – M energized

ON

ON

Control normal operation – no communication or call for

compressor present

No faults active, Y1 or Y2 not present

OFF

2s ON / 2s OFF

Control normal operation – in ASCD period

No faults active, Y1 or Y2 present,

ASCD timer not expired

OFF

0.1 sec ON /

0.1 sec OFF

TABLE 5: Status Code Display

Description

Required Condition

LED3 (Yellow)

Control normal operation – with active communication present

System is active and presently communicating successfully.

0.1 sec ON /

0.1 sec OFF

Control powered – without active communication present

System has 24 VAC present and the microprocessor is active. 2s ON / 2s OFF