Emerson OpenComms-485 User Manual

Page 20

Advertising
background image

REV. 5

7/6/2007

Liebert Monitoring Group –Development

17

Ambient Temperature
Warning Point

30069

40069

1

1

deg C

Over Temperature Limit
Point 30072

40072

1

1

deg

C

Load (Apparent Power)

30102

2

1

VA

Load (Real Power)

30104

2

1

W

Load / Capacity

30106

1

1

%

Input Frequency

30107

1

10

Hz

Output Frequency

30108

1

10 Hz

Battery Charge Status

30112

1

1 - 100% Charged
2 - Less than 100%
Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging

Battery Voltage

30113

1

1

V

Battery Time Remaining

30115

1

1

min

Battery Charge
Percentage

30116

1

1

%

Ambient Temperature

30119

1

1

deg C

Battery Test Result

30130

1

1

Input Voltage L1

30153

1

1

V

Input Current L1

30154

1

1

A

Output Voltage L1

30163

1

1

V

Output Current L1

30164

1

1

A

Input Maximum Voltage
L1

30180

1

1

V

Input Minimum Voltage
L1

30181

1

1

V

Output Maximum
Voltage L1

30182

1

1

V

Output Minimum
Voltage L1

30183

1

1

V

Black Out Count

30301

1

1

Brown Out Count

30302

1

1

Advertising