Liebert ds, Data points mapped to input status and coils – Emerson OpenComms-485 User Manual

Page 32

Advertising
background image

REV. 5

7/6/2007

Liebert Monitoring Group –Development

29

Liebert DS

Data points Mapped to Input Status and Coils

Reference Document: ST100I&C PA Parameters and Events, Version 18.0

Data Description

Status

Coil#

#

bit

-

Notes

iCOM
Reference

Sleep on Monday

10001

1

1

U603

Sleep on Tuesday

10002

2

1

U603

Sleep on Wednesday

10003

3

1

U603

Sleep on Thursday

10004

4

1

U603

Sleep on Friday

10005

5

1

U603

Sleep on Saturday

10006

6

1

U603

Sleep on Sunday

10007

7

1

U603

Supply Limit Enable

10008

8

1

S105

Reheat Lockout

10009

9

1

S271

Humidifier Lockout

10010

10

1

S272

Temperature Indication [1]

10011

11

1

U404

Timer Mode Type

10012

12

1

U610

Minimum Chilled Water Temp
Enable

10013

13

1

S128

Std. Sensor Alarms Enable

10019

19

1

U202

Sensor A Alarms Enable

10020

20

1

U207

Compressor Lockout

10021

21

1

S274

VSD Fan speed

10022

22

1

S131

Unit Control

-

25

1

EnvState.
SysCtrl

Reset Alarm

-

26

1

..

EnvState.
AlarmCtrl.1

Acknowledge Alarm

-

27

1

..

EnvState.
AlarmCtrl.2

Reset Total Run Hours Fan
Motor

-

28

1

..

U502

Reset Comp1Run Hour

-

29

1

..

U503

Reset Comp2Run Hour

-

30

1

..

U504

Reset Humidifier Run Hour

-

31

1

..

U510

Reset Dehumidifier Run Hour

-

32

1

..

U511

Reset CW/FC Run Hour

-

33

1

..

U505

Reset E-Heater1RunHour

-

34

1

..

U507

Reset E-heater2RunHour

-

35

1

..

U508

Reset E-heater3 Run Hour

-

36

1

..

U509

Reset HG/HW Run Hour

-

37

1

..

U506

Fan On

10025

-

1

FanSym

Cool On

10026

-

1

CoolSym

Free Cool On

10027

-

1

FCSym

Hot Water On

10028

-

1

HWSym

Electrical Heater On

10029

-

1

HeatSym

Advertising