Diagnostics and troubleshooting, Reading status data from the module, Definition of module's extended diagnostics data – ProSoft Technology MVI56-PDPS User Manual

Page 41: E 41), 4 diagnostics and troubleshooting

Advertising
background image

Diagnostics and Troubleshooting

MVI56-PDPS ♦ ControlLogix Platform

Profibus DP Slave Communication Module

ProSoft Technology, Inc.

Page 41 of 88

April 22, 2008

4 Diagnostics

and

Troubleshooting

In This Chapter

™

Reading Status Data from the Module .................................................. 41

™

LED

Indicators....................................................................................... 53

The module provides information on diagnostics and troubleshooting in the
following forms:
ƒ

Status data values are transferred from the module to the processor.

ƒ

Data contained in the module can be viewed through the

Configuration/Debug port attached to a terminal emulator.

ƒ

LED status indicators on the front of the module provide information on the

module's status.

4.1

Reading Status Data from the Module

The MVI56-PDPS module returns a 20-word Status Data block that can be used
to determine the module's operating status. This data can be located in the
module's database at registers at the location specified in the configuration. This
data is transferred to the ControlLogix processor continuously with each read
block.

4.1.1 Definition

of

Module's Extended Diagnostics Data

The Extended Diagnostic Data is reported during startup and initialization
sequence when the master requests diagnostic data from the module. The
Extended Diagnostics is "Device Related" type providing status data (the
extended diagnostic bit 3 in standard diagnostic byte 1 is set = 0). The data
length is normally 14 (0E) bytes displayed in the following format:

Byte(s) Description

(HEX)

0

Extended Diagnostics length (normally 14 bytes (0E))

1 to 6

ASCII data for Product Version

7 to 10

ASCII data for Product Name

11

Value of Status Register [0] (see Section 2)

12

Value of Status Register [1] (see Section 2)

13

Module State (see Section 2)

Byte 10 Data - Specific Product Code Value

34 = ASCII "4" = MVI46

35 = ASCII "5" = MVI56

36 = ASCII "6" = MVI69

37 = ASCII "7" = MVI71