SlotServer Supplement – LonWorks Open Profile

Page 6 of 16

ProSoft Technology, Inc. is the exclusive provider of FieldServer SlotServers.

For Technical Support call +1 661.716.5100

4

COMMISSIONING THE OPEN PROFILE ON THE SLOTSERVER

The following steps are necessary to connect LonWorks Data to the PLC CPU via the SlotServer.

4.1

Write Ladder Program to Get LonWorks Input Data

Add a CPS (Synchronous Copy File) Ladder element to synchronize the incoming Data from the LonWorks
network. Use the Input Image Data as Source.

Create the Destination Tag by
right clicking on Destination
and choosing New Tag.

Create a Controller Tag of Type
REAL, dimension 80 for the
Destination