Led status indicators, Status, Indicators – ProSoft Technology MVI46-GSC User Manual

Page 37

Advertising
background image

Diagnostics and Troubleshooting

MVI46-GSC ♦ SLC Platform

Generic Serial Communication Module

ProSoft Technology, Inc.

Page 37 of 78

December 5, 2007

You have now captured, and saved the file to your PC. This file can now be used
in analyzing the communications traffic on the line, and assist in determining
communication errors.

4.2

LED Status Indicators

The LEDs indicate the module's operating status as follows:

ProSoft
Module

Color Status Indication

On

Data is being transferred between the module and a remote
terminal using the Configuration/Debug port.

CFG Green

Off

No data is being transferred on the Configuration/Debug port.

On

Data is being transferred between the module and the serial
network on its Port 1.

P1 Green

Off

No data is being transferred on the port.

On

Data is being transferred between the module and the serial
network on its Port 2.

P2 Green

Off

No data is being transferred on the port.

Off

The MVI46-GSC module program has recognized a
communication error on one of its ports or the SLC is not in run
mode.

APP Amber

On

The MVI46-GSC is working normally.

On

The LED is on when the module is performing a write operation
on the backplane.

BP ACT

Amber

Off

The LED is off when the module is performing a read operation
on the backplane. Under normal operation, the LED should
blink rapidly on and off.

Off

The card is not receiving any power and is not securely
plugged into the rack.

Green

The module is operating normally.

OK Red/

Green

Red

The program has detected an error or is being configured. If the
LED remains red for over 10 seconds, the program has
probably halted. Turn off the power to the rack, remove the
card from the rack and re-insert the card to restart the module's
program. Restore power to the rack.

Off

The battery voltage is OK and functioning.

BAT Red

On

The battery voltage is low or battery is not present. Allow
battery to charge by keeping module plugged into rack for 24
hours. If BAT LED still does not go off, contact the factory, as
this is not a user serviceable item.