PLX3x Series

MBS Protocol

Ethernet and Serial Gateways

User Manual

ProSoft Technology, Inc.

Page 131 of 218

September 17, 2014

Parameter

Value

Description

o

For Coil address 00115, specify 114

o

(00115 - 00001 = 114)

For register read or write commands (FC 3, 6, or 16) 4X range,
for 40001, specify a value of 0
o

(40001 - 40001 = 0).

For 01101, 11101, 31101 or 41101, specify a value of 1100.
o

(01101 - 00001 = 1100)

o

(11101 -10001 = 1100)

o

(31101 - 30001 = 1100)

o

(41101 - 40001 = 1100)

Note: If the documentation for a particular Modbus server device
lists data addresses in hexadecimal (base16) notation, you will need
to convert the hexadecimal value to a decimal value to enter in this
parameter. In such cases, it is not usually necessary to subtract 1
from the converted decimal number, as this addressing scheme
typically uses the exact offset address expressed as a hexadecimal
number.