Saving the current configuration, Configuring the an-x module in rslogix 5000 – ProSoft Technology AN-X2-GENI User Manual

Page 37

Advertising
background image

AN-X2-GENI (AN-X-GENI/B) Page

31

22: 0 2 BlockErr

23: 2 1 b01 b01_Inp 16-Ckt Normally-open Relay Block

24: 3 1 b02 b02_Inp 24/48VDC 16 Ckt Source I/O Block

25: 4 4 b03 b03_Inp 24/48VDC 4In/2Out Analog Block

26: 8 12 b09 b09_Inp Genius Bus Interface Unit

27: 20 8 b16 b16_Inp Series 90-30 Bus Controller

28: 28 2 b22 b22_Inp 12/24VDC 32 Ckt Source I/O Block

29: 30 64 b31 b31_Inp Series 90-70 Bus Controller

48: ClxSlot 15

50: DataInput

51: 0 2 BlockFlt

52: 10 10 DiagCtrs

55: 20 10 ConnStats0

......Parse Successful

Each line begins with a line number, from the original ControlLogix configuration file.
Each mapping line shows the offset and length of the data in the ControlLogix data
connection.

Saving the Current Configuration

To save the ControlLogix configuration currently stored in the AN-X to a file, start the
web interface and select Automation Network/View Active Configuration.

Right click the Ethernet/IP link and select Save target to save the current ControlLogix
scheduled data configuration to a file.

You can also save the ControlLogix configuration by selecting Automation Network/View
Configuration Files
. Right click on the AN-X2-GENI ControlLogix Configuration File
link and select Save target to save the current ControlLogix scheduled data configuration
to a file.

Configuring the AN-X Module in RSLogix 5000

To configure the AN-X2-GENI in RSLogix 5000:

1. Right click on the ControlLogix Ethernet module that will be communicating to the

AN-X and select Add Module. Add a 1756-ENBT/A module.

2. Set the Major Rev to 1.