Installation, Ad c b – Enviro 2100 Freestanding User Manual

Page 11

Advertising
background image

11

Installation

C

HIMNEY

I

NSTALLATION

T

HROUGH

W

ALL

:

Here are four methods of combustible wall chimney connector pass-throughs. This information was provided from

NFPA 211.

Method A. 12” (304.8 mm) Clearance to Combustible Wall

Member: Using a minimum thickness 3.5” (89 mm) brick and

a 5⁄8” (15.9 mm) minimum wall thickness clay liner, construct a

wall pass-through. The clay liner must conform to ASTM C315

(Standard Specification for Clay Fire Linings) or its equivalent. Keep

a minimum of 12” (305 mm) of brick masonry between the clay

liner and wall combustibles. The clay liner shall run from the brick

masonry outer surface to the inner surface of the chimney flue liner

but not past the inner surface. Firmly grout or cement the clay liner

in place to the chimney flue liner.
Method B. 9” (229 mm) Clearance to Combustible Wall Member:

Using a 6” (152 mm) inside diameter, factory-built Solid-Pak chimney

section with insulation of 1” (25.4 mm) or more, build a wall pass-

through with a minimum 9” (229 mm) air space between the outer

wall of the chimney length and wall combustibles. Use sheet metal

supports fastened securely to wall surfaces on all sides, to maintain

the 9” (229 mm) air space. When fastening supports to chimney

length, do not penetrate the chimney liner (the inside wall of the

Solid-Pak chimney). The inner end of the Solid-Pak chimney section

shall be flush with the inside of the masonry chimney flue, and

sealed with a non-water soluble refractory cement. Use this cement to also seal to the brick masonry penetration.

A

D

C

B

Method C. 6” (152.4 mm) Clearance to Combustible Wall Member:

Starting with a minimum 24 gauge (.024” [0.6 mm]) 6” (152.4 mm)

metal chimney connector, and a minimum 24 gauge ventilated wall

thimble which has two air channels of 1” (25.4 mm) each, construct

a wall pass-through. There shall be a minimum 6” (152.4 mm)

separation area containing fiberglass insulation, from the outer

surface of the wall thimble to wall combustibles. Support the wall

thimble, and cover its opening with a 24 gauge minimum sheet

metal support. Maintain the 6” (152.4 mm) space. There should

also be a support sized to fit and hold the metal chimney connector.

See that the supports are fastened securely to wall surfaces on all

sides. Make sure fasteners used to secure the metal chimney connector do not penetrate chimney flue liner.

Method D. 2” (50.8 mm) Clearance to Combustible Wall Member:

Start with a solid-pak listed factory built chimney section at least

12” (304 mm) long, with insulation of 1” (25.4 mm) or more, and

an inside diameter of 8” (2” [51 mm] larger than the 6” [152.4 mm]

chimney connector). Use this as a pass-through for a minimum 24

gauge single wall steel chimney connector. Keep solid-pak section

concentric with and spaced 1” (25.4 mm) off the chimney connector

by way of sheet metal support plates at both ends of chimney

section. Cover opening with and support chimney section on both

sides with 24 gauge minimum sheet metal supports. See that the

supports are fastened securely to wall surfaces on all sides. Make

sure fasteners used to secure chimney flue liner.

NOTES:

1. Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall

pass-through system and the chimney wall, to but not past the inner flue liner face.

2. A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a floor,

or ceiling.

Advertising