Software and accessories – Eaton Electrical CA04801001E User Manual

Page 12

Advertising
background image

March 2008

12

For more information visit: www.eaton.com

CA04801001E

Operator Interface Products
HMi
Operator Interface

Software and Accessories

Table 12. HMIEC0806/HMIEC1612 Function Specifications

ᕃ

M1000, M1001, M1002, M1003, M1020, M1021, M1022, M1067, M10068, and M1161 are the
special auxiliary relays (special M).

Item

Specifications

Remark

Control Method

Stored program, cyclic
scan system

—

I/O Processing Method

Batch I/O (refresh)

Immediate refresh command available only
with I/O of the MPU

Execution Speed

Basic command (30 us)

Application command (30 ~ hundreds us)

Program Language

Commands + Ladder
Diagram + SFC

Step commands included

Program Capacity

999 Steps

Built-in EEPROM

Commands

Basic commands: 32
(including the STL
commands)

Application commands: 59

Step Relay
(Latched)

General Step
Point

128 Points

S0 ~ S127

Auxiliary
Relay

General

1024 Points

M0 ~ M511, M768 ~ M999, 744 points;
M1000 ~ M1279, 280 points

ᕃ

Latched

256 Points

M512 ~ M767

Timer

Digital

64 Points

T0 ~ T63 (100 ms time base)

63 Points

T64 ~ T126 (10 ms time base)

1 Points

T127 (1 ms time base)

Counter

General

112 Points

C0 ~ C111

Latched

16 Points

C112 ~ C127

32 bit

13 Points

C235,C236,C237,C238,C241,C242,
C244,C246,C247,C249,C251,C252, C254
(all of them are latched type)

Data
Register

General

408 Points

D0 ~ D407

Latched

192 Points

D408 ~ D599

Pointer

P

64 Points

P0 ~ P63

Index
Register

E / F

2

E, F

Constant

Decimal K

16 bit: -32768 ~ +32767

32 bit: -2147483648 ~ +2147483647

Hexadecimal H 16 bit: 0000 ~ FFFF

32 bit: 00000000 ~ FFFFFFFF

Self Diagnosis / Protection

I/O check, system execution timeout check, invalid command check,
program check and password settings

Monitor / Debug

Program execution time display, bit / word, device settings

Advertising