Chimney installation through wall, Installation – Enviro Kodiak 1700 Freestanding User Manual

Page 22

Advertising
background image

Installation

C

HIMNEY

I

NSTALLATION

T

HROUGH

W

ALL

:

Here are four (4) methods of combustible wall chimney connector pass-throughs. Information was provided from NFPA 211.

Method A. 12” (304.8 mm) Clearance to Combustible Wall Member:

Using a minimum thickness 3.5” (89 mm) brick and a 5⁄8” (15.9 mm)

minimum wall thickness clay liner, construct a wall pass-through. The

clay liner must conform to ASTM C315 (Standard Specification for Clay

Fire Linings) or its equivalent. Keep a minimum of 12” (305 mm) of brick

masonry between the clay liner and wall combustibles. The clay liner

shall run from the brick masonry outer surface to the inner surface of the

chimney flue liner but not past the inner surface. Firmly grout or cement

the clay liner in place to the chimney flue liner.

Method B. 9” (229 mm) Clearance to Combustible Wall Member: Using

a 6” (152 mm) inside diameter, factory-built Solid-Pak chimney section

with insulation of 1” (25.4 mm) or more, build a wall pass-through with a

minimum 9” (229 mm) air space between the outer wall of the chimney

length and wall combustibles. Use sheet metal supports, fastened

securely to wall surfaces on all sides, to maintain the 9” (229 mm) air

space. When fastening supports to chimney length, do not penetrate

the chimney liner (the inside wall of the Solid-Pak chimney). The inner

end of the Solid-Pak chimney section shall be flush with the inside of the

masonry chimney flue and sealed with a non-water soluble refractory

cement. Use this cement to also seal to the brick masonry penetration.

Method C. 6” (152.4 mm) Clearance to Combustible Wall Member:

Starting with a minimum 24 gauge (.024” [0.6 mm]) 6” (152.4 mm)

metal chimney connector and a minimum 24 gauge ventilated wall

thimble which has two air channels of 1” (25.4 mm) each, construct a

wall pass-through. There shall be a minimum 6” (152.4 mm) separation

area containing fiberglass insulation, from the outer surface of the wall

thimble to wall combustibles. Support the wall thimble and cover its

opening with a 24 gauge minimum sheet metal support. Maintain the

6” (152.4 mm) space. There should also be a support sized to fit and

hold the metal chimney connector. See that the supports are fastened

securely to wall surfaces on all sides. Make sure fasteners used to secure

the metal chimney connector do not penetrate chimney flue liner.

Method D. 2” (50.8 mm) Clearance to Combustible Wall Member: Start
with a solid-pak listed factory-built chimney section at least 12” (304 mm)
long, with insulation of 1” (25.4 mm) or more, and an inside diameter of
8” (2” [51 mm] larger than the 6” [152.4 mm] chimney connector). Use
this as a pass-through for a minimum 24 gauge single-wall steel chimney
connector. Keep solid-pak section concentric with and spaced 1” (25.4
mm) off the chimney connector by way of sheet metal support plates
at both ends of chimney section. Cover opening, and support chimney
section on both sides, with 24 gauge minimum sheet metal supports.
See that the supports are fastened securely to wall surfaces on all sides.

Make sure fasteners are used to secure chimney flue liner.

NOTES:

1. Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall pass-through

system and the chimney wall, to but not past the inner flue liner face.

2. A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a floor, or ceiling.

Figure 18: Chimney Through Wall - Method A.

Figure 19: Chimney Through Wall - Method B.

Figure 21: Chimney Through Wall - Method D.

Figure 20: Chimney Through Wall - Method C.

22