Integrated distribution cabinet (idc), Simplified installation and clean appearance, Features – Eaton Electrical 9390 User Manual

Page 12

Advertising
background image

12

EATON CORPORATION Eaton 9390 Uninterruptible Power System

• Maintenance bypass enables

power to completely bypass
the UPS power module. You
can then service or replace
the module in complete safe-
ty, without interrupting power
to critical systems.

Maintenance bypass is internally
wired at the factory inside the
IDC so that only input cables
and UPS connections need to
be made in the field.

Simplified installation
and clean appearance

The IDC has the same look and
finish as the 9390 it compli-
ments. The cabinet is shipped
with interconnecting cables
for fast and easy installation.
The result is a clean look that
enhances the appearance of
your data center.

Integrated manage-
ment and support for
enhanced confidence

The 9390 and the IDC can all
be monitored and managed by
LanSafe

®

, PowerVision

®

, and

FORESEER

®

software. This

close integration provides great-
er visibility to your complete
power protection and distribu-
tion structure.

Eaton backs up the IDC with the
same one-year limited factory
warranty

*

we offer on the 9390

UPS models. You can have both
the confidence that both your
power protection and distribu-
tion are supported by Eaton’s
best-in-class service organization
and strong customer service
commitments.

* See the Limited Factory Warranty for 9390 products for details.

40-80 kVA IDC Bypass/transformer/

distribution cabinet

Integrated
Distribution
Cabinet (IDC)

The Eaton IDC is specifically
designed to compliment the
9390. With this optional cabinet,
Eaton offers a complete, one-
stop shop for power protection
and distribution solutions that is
easy to design, install, custom-
ize and manage – while deliver-
ing pay-as-you-grow scalability
for future expansion.

Pre-configured for ease
of use, mix-and-match
for flexibility

The IDC is pre-configured with
the most popular power distribu-
tion options for ease of design
and installation. In addition, the
IDC also offers the flexibility to
mix and match power distribu-
tion, voltage transformation and
maintenance bypass options to
select the right combination of
the following capabilities for your
data center requirements:

• Power distribution options

enable you to distribute
power to servers or racks
via distribution panelboards
or distribute power to larger
loads via distribution circuit
breakers or terminal blocks.

• Voltage transformation allows

you to change output voltage
levels. For instance, you could
convert 480 Vac output from
the UPS into 208/120 Vac
output from the UPS to serve
data center loads. K-rated
transformers are available
to support loads with high
harmonic content.

Features

• Two, three or four-breaker maintenance bypass

• Transformer options up to K20

• (2) 42-pole panelboards

Or

• (1) 42-pole panelboard and up to (3) 250A distribution breakers

Or

• Up to (6) 250A distribution breakers

• Line and match or remote

• Casters and leveling feet

• Panelboards come with individual 225A main breaker

• Neutral rated for harmonic loads (200%)

• Distribution breakers are Eaton JG electronic trip

- Two electronic sensors available 100A and 250A
- 100A settings 40-100A trip (eight settings)
- 250A setting 100-250A trip (eight settings)