Energy efficiency means substantial cost savings

All UPSs consume energy to operate, and some unused energy is dissipated as heat as it passes through the UPS—the more heat
and dissipated energy, the higher cost of operation. The efficiency rating of a UPS measures how little energy is wasted.

For exam-

ple, a 90% efficient UPS delivers 90 kW of useful power for every 100 kW taken in. With a transformerless design and sophisticated
sensing and control circuitry, the 9390 delivers an efficiency of up to 94 percent with double-conversion protection. In addition to the
cost savings, this enhanced efficiency extends battery runtimes and produces cooler UPS operating temperatures, extending compo-
nent life and increasing reliability and performance.

Comparison of 90% versus 94% efficient 80 kVA UPS

Percent

Wasted kW

Cost per kWh

Extra energy

Extra air

Annual savings vs.

efficiency

hours*

and demand

cost

conditioning cost

less-efficient model

90

63,072

$0.13

$8,199

$5,740

94

37,843

$0.13

$4,919

$3,444

$5,576

* Mostly dissipated as heat.

Power performance

Input

THD

Output

PF

Efficiency

Eaton 9390

<4.5%

0.9

94%

Competitor “A”

<7.5%*

0.8

92.5-93%

Competitor “B”

<10%*

0.8

90-95%

Competitor “C”

<10%*

0.8

92-93%

Competitor “D”

<7%*

0.8

87-93%

Competitor “E”

<7%*

0.8

90-93.3%

Competitor “F”

<3%

0.8

88.5-94%

Competitor “G”

<3-7%

0.8

87% (estimated)

*w/filter (~30% w/out)

80

100

160 kVA @ 480V

100

90

80

70

60

50

40

30

20

10

82

84

86

88

90

92

94

96

98

94.65%

% Load

Eaton 9390 160 kVA Efficiency Curve

% Ef

ficiency

Operational savings

Efficiency comparison

Efficiency

difference:

2%

3%

4%

1 year

5 years

1 year

5 years

1 year

5 years

Savings–80 kVA UPS

$2,788 $13,940

$4,182

$20,910

$5,576

$27,880

Savings–160 kVA UPS

$5,576 $27,880

$8,363 $41,815

$11,151

$55,755

CO

2

Savings–80 kVA

19.3 tons 96.5 tons

23.1 tons 115.5 tons

26.9 tons 134.5 tons

CO

2

Savings–160 kVA

26.9 tons 134.5 tons

34.5 tons 172.5 tons

42.2 tons

211 tons

Alternative voltages for IT data center powering

In addition to conventional (208 and 480) voltage capabilities, the 9390 now has the ability to support direct-
connect 400/230 Vac for powering directly to the IT rack. This capability allows for the deployment of a UL/CE
rated UPS that can protect and distribute 400/230 Vac directly to IT racks without an additional step-down
transformer. Some of the efficiencies and benefits of this alternative voltage powering are:

• Elimination of the step-down 480-208 volt transformer lowers heat losses and saves valuable floor space

in the data center

• Higher voltage directly to IT equipment allows it to operate at higher efficiency (no changes required, as

virtually all servers are rated to operate at up to 240 Vac)

• No changes to power distribution equipment since connectors and circuit breakers already exist with

these ratings

• The use of Eaton’s high efficiency 9390 UPS in such an application further improves system overall efficiency.

• Multiple studies show that up to 5% overall efficiency gains can be made versus equivalent 480 or 208 Vac

systems, resulting in thousands of dollars in savings per year.