B. Constructing the Appliance Chase

A chase is a vertical box-like structure built to enclose the

gas appliance and/or its vent system. In cooler climates

the vent should be enclosed inside the chase.
NOTICE: Treatment of ceiling fi restops and wall shield

fi restops and construction of the chase may vary with the

type of building. These instructions are not substitutes

for the requirements of local building codes. Therefore,

you MUST check local building codes to determine the

requirements to these steps.
Chases should be constructed in the manner of all out-

side walls of the home to prevent cold air drafting prob-

lems. The chase should not break the outside building

envelope in any manner.
Walls, ceiling, base plate and cantilever fl oor of the chase

should be insulated. Vapor and air infi ltration barriers

should be installed in the chase as per regional codes for

the rest of the home. Additionally, in regions where cold

air infi ltration may be an issue, the inside surfaces may be

sheetrocked and taped for maximum air tightness.
To further prevent drafts, the wall shield and ceiling fi re-

stops should be caulked with caulk with a minimum of

Figure 5.2 Clearances to Combustibles

C. Clearances

NOTICE: Install appliance on hard metal or wood surfaces

extending full width and depth.

DO NOT install directly

on carpeting, vinyl, tile or any combustible material other

than wood.
WARNING! Risk of Fire! Maintain specifi ed air space

clearances to appliance and vent pipe:
• Insulation and other materials must be secured to prevent

accidental contact.

• The chase must be properly blocked to prevent blown

insulation or other combustibles from entering and

making contact with fi replace or chimney.

• Failure to maintain airspace may cause overheating and

a fi re.

300ºF continuous exposure rating to seal gaps. Gas line

holes and other openings should be caulked with caulk

with a minimum of 300ºF continuous exposure rating or

stuffed with unfaced insulation. If the appliance is being

installed on a cement surface, a layer of plywood may be

placed underneath to prevent conducting cold up into the

room.

* Adjust framing dimensions for interior sheathing (such as sheetrock)

C

D

B

A

E

H

I

F

J

G

FROM APPLIANCE

OPENING TO CEILING

* MINIMUM FRAMING DIMENSIONS

A

B

C

D

E

F

G

H

I

J

Rough

Opening

(Vent Pipe)

Rough

Opening

(Height)

Rough

Opening

(Depth)

Rough

Opening

(Width)

Clearance

to Ceiling

Combustible

Floor

Combustible

Flooring

Behind

Appliance

Sides of

Appliance

Front of

Appliance

Inches

10

52-1/2

22

57-1/2

43

0

12

1/2

1/2

36

mm

254

1334

559

1461

1092

0

305

13

13

914