7800 SERIES S7810B MULTI-DROP SWITCH MODULE

3

65-0228—3

Canadian EMI: This digital apparatus does not exceed the

Class A limits for radio noise emission from digital apparatus

set out in the Radio Interference Regulations of the Canadian

Department of Communications.

Le présent appareil numérique n’émet pas de bruits

radioélectriques dépassant les limites applicables aux

appareils numériques de la Classe A prescrites dans le

Règlement sur le brouillage radioeléctrique édicté par le

ministère des Communications du Canada.

Humidity

Install the S7810B where the relative humidity never reaches

the saturation point. The S7810B is designed to operate in a

maximum humidity environment of 85 percent relative humidity

continuous, noncondensing moisture.

Weather

The S7810B is not designed to be weather-tight. When

installed outdoors, protect the S7810B with an approved

weather-tight enclosure.

Vibration

Do not install the S7810B where it could be subjected to

vibration in excess of 0.5G continuous maximum vibration.

Mounting the S7810B Multi-Drop Switch

Module.

1. Align the two ears of the Multi-Drop Switch Module with

the two mating slots on the 7800 SERIES Relay Module.

2. Insert the two interlocking ears into the two mating slots

and, with a hinge action, push on the lower corners of

the Multi-Drop Switch Module to secure it to the 7800

SERIES Relay Module.

Wiring (Fig. 2)

1. Refer to Fig. 2 for proper wiring.

2. All wiring must comply with all applicable electrical

codes, ordinances and regulations.

3. Recommended wiring size and type:

a. For ControlBus™ communications, use 22 AWG,

3-wire shielded cable (Belden part number 8723 or

equivalent).

b. For 13 Vdc and remote reset switch operation, use

22 AWG wire insulated for voltages and

temperatures in the application. Suggested wire

types include TW (60°C), THW (75°C) and THHN

(90°C) Terminal identification numbers and letters

shown in Table 1.

Table 1. S7810B and QS7800B Terminal Identification.

4. Wire routing:

a. Do not route the ControlBusª cable in conduit with

line voltage circuits.

b. Do not route the ControlBusª cable close to the

ignition transformers.

c. Route the ControlBusª cable outside of conduit if

properly supported and protected from damage.

d. Route the ControlBusª cable so that all devices are

connected in a daisy chain configuration. See Fig. 3.

5. Maximum wire lengths:

a. RS-485 Communications bus, 4000 feet

(1219 meters).

b. Remote reset switch, 1000 feet (305 meters).

BUILDING A MULTI-DROP NETWORK

The subnetwork addressing in the Q7700 Network Interface

Unit (NIU) is not contiguous. It is divided into two blocks,

containing 198 and 24 addresses, respectively. A maximum

multi-drop configuration would include 222 subnetworks

(198 plus 24) on a single Q7700 NIU.

One QS7800B ControlBusª Module card supports up to 31

multi-drop subnetworks without using an RS-485 repeater. If

an RS-485 repeater is used, up to 61 multi-drop subnetworks

can be supported by one QS7800B card. The RS-485 repeater

must be installed between the 30th and 31st subnetworks.

Each subnetwork includes one 7800 SERIES controller with or

without an S7800 Keyboard Display Module and/or an S7830

Expanded Annunciator. An S7810B1007 Multi-Drop Switch

Module is required in each subnetwork. See Fig. 3 for wiring

information.

Subnetworks can be spread evenly (balanced) across the NIU

slots to improve speed of communications.

It is recommended that the multi-drop network be built starting

with slot number 1 of the NIU, subject to the above guidelines.

Record the serial number and physical location of each

S7810B Multi-Drop Switch. This data will be useful when

commissioning the ZM7850 Combustion System Manager

(CSM) software. Refer to CSM manual, form 65-0102, for CSM

commissioning.

Signal

S7810B

Terminal

QS7800B

Terminal

Local Bus Data +

1

None

Local Bus Data -

2

None

Common

• Local Bus Common

• +13 Vdc Common

• Remote Reset Common

3

None

+13 Vdc

4

None

Remote Reset

5

None

Multi-Drop Bus Common

6

c

Multi-Drop Bus Data +

7

a

Multi-Drop Bus Data -

8

b