Quickspecs – HP EVA4100 User Manual

Page 48

Advertising
background image

Management Software Command View EVA v7.0 or v8.0 used with the Storage Management Appliance software v2.1 running

on the HP OpenView Storage Management Appliance (SMA) or with a server in the SAN running
Microsoft Windows.

Disk Drives, Interface

Dual-port 2/4 Gb/s FC-AL

Dual-port 2/4 Gb/s FC-AL

Dual-port 2/4 Gb/s FC-AL

Disk Drives Enclosure

14 bay switched enclosure

14 bay switched enclosure

14 bay switched enclosure

NOTE: EVA4100 Starter Kits comes pre-configured with a 2C1D, 8-146GB 15K or 300GB 10K rpm HDDs Command View EVA
software with licensing up to 4TBs. The EVA4100 Starter Kit for HP BladeSystems comes pre-configured with a 2C1D and Command
View software with licensing up to 4TB's.

EVA4100

EVA6100

EVA8100

Operating Temperature

50° to 95° F (10° to 35° C) - Reduce rating by 1° F for each 1000 ft altitude (1.8° C/1,000 m)

Shipping Temperature

-40° to 150° F (-40° to 66° C)

Humidity

10% to 90% non-condensing

Shipping Humidity

5% to 90% non-condensing

Altitude

Up to 8,000 ft (2,400 m)

Air Quality

Not to exceed 500,000 particles per cubic foot of air at a size of 0.5 micron or larger

Power Data (North America/Europe/Japan) maximum configuration

EVA4100

EVA6100

EVA8100

AC plug type
(quantity 2)

North America-3 wire NEMA No. L6-30P, 30 Amp (208 to 240V, 50-60Hz 30A)

Europe - 3 wire, 2 pole IEC 309, 30 amp, (220 to 240V 50Hz 32A)

Number of phases

Single

Rated current

17A @ 200V-240V AC, 60Hz total, 4.25 A per power cord

Nominal Line Voltage

North America - 208 or 230V

Europe - 230V

Japan - 206V

Range Line Voltage

187 to 256V

Line Frequency

North America 60Hz, Europe 50Hz, Japan 50 or 60 Hz

Enterprise Virtual Array 4100 and 4100 Starter Kits

NOTE: This data represents fully populated
drive shelves with 15K rpm disk drives. Other
drive types may vary slightly.

208 Volts

230 Volts

2C1D

2C2D

2C3D

2C4D

2C1D

2C2D

2C3D

2C4D

Typical

Total System Wattage

638

1013

1390

1767

638

1013

1390

1767

Total System BTU/hour

1729

3014

4300

5585

1729

3014

4300

5585

Input Current (A) -
Typical per system

1.6

2.6

3.5

4.4

1.5

2.4

3.3

4.2

In Rush Current (A)

98

132

170

220

104

147

190

244

Failover Mode Input Current (A) -

Maximum per system

2.7

4.3

5.9

7.5

2.6

4.1

5.5

7.1

NOTE: Typical is described as a system in normal steady state operation. (I.e., both PDUs operating normally, the array
reading/writing to disk drives in a production environment)

QuickSpecs

HP StorageWorks Enterprise Virtual Array Family

Technical Specifications

DA - 12745 Worldwide QuickSpecs — Version 5 — 2.26.2008

Page 48

Advertising
This manual is related to the following products: