Planning the installation, Selecting mounting position and location, Planning ducting – Honeywell F500 User Manual

Page 3

Advertising
background image

F500 WHOLE HOUSE/ LIGHT COMMERCIAL HEPA FILTRATION SYSTEM

3

68-0263-2

PLANNING THE INSTALLATION

Selecting Mounting Position and Location

The F500 can be suspended from exposed ceiling joists or the
ceiling surface, or it can be floor-mounted.

1.

Install the F500A in a conditioned space or the F500B in
an unconditioned space using these guidelines.

2.

Plan the unit location to minimize duct lengths.

3.

Locate an existing electrical outlet with the appropriate
current rating to plug in the power cord. (If an outlet is
not available, have a qualified electrician install one.)

4.

Choose a location that is readily accessible for checking
and replacing the filter. (Allow at least 26-1/2 in. (673
mm) clearance in front of the unit.)

Planning Ducting

The F500 can be mounted to the whole-house forced air
system using a bypass configuration or can be independently
ducted to stand alone. See Fig. 2, 3, and 4 for typical
installations.

The Whole House/Light Commercial HEPA air cleaner has
4 in. x 10 in. duct flanges to easily attach the external
ductwork.

The intake port can be moved to a more convenient
location, if necessary:

Simply cut a new 4 in. x 10 in. hole in the desired loca-
tion and block off the old hole.

Reattach the duct flange over the new hole.

A transition can be used to connect round ducting to the
Whole House/Light Commercial HEPA System.

Keep duct sizes as large as possible throughout the
installation (8 in. minimum diameter ducting is recom-
mended).

Keep intake and exhaust duct runs as short as possi-
ble with few bends or elbows.

The F500 can be installed with a heat recovery ventilator.
See Fig. 4.

Fig. 2. Typical F500 bypass installation.

Fig. 3. Typical F500 independent installation.

Table 1. Replacement Media Recommendations.

Filter (in in.)

Part Number

Replacement Interval

Normal

Light Duty

Carbon-Odor Filter (24 x 12)

32006026-001

3 months

4 months

Pleated Prefilter (24 x 12 x 2)

32006027-001

12 months

16 months

HEPA Filter (24 x 12)

32006028-001

3 years

5 years

S688A1007
SAIL SWITCH
(OPTIONAL)

HIGH EFFICIENCY

AIR CLEANER

120 VAC 60 HZ SUPPLY WITH GROUND

M20263A

RETURN AIR

F500

AIR

HANDLER

(FURNACE)

15 AMP LIGHT SWITCH

120 VAC 60 HZ SUPPLY WITH GROUND

M20579

F500

Advertising