F90A,B SELF-CONTAINED COMMERCIAL ELECTRONIC AIR CLEANER

68-0103-6 Revised 11-07

5

STAGE

DANCE FLOOR

T
A
B
L
E
S

BAR

LOW SMOKING LEVEL AT
STAGE AND DANCE FLOOR.
USE ONE F90.

HEAVY SMOKING LEVEL AT
TABLES AND BAR.
USE THREE F90s.

M1528A

F90

F90

F90

F90

F90

F90

F90

F90

F90

F90

Fig. 4. F90 mounting considerations.

M923

Fig. 5. F90 Coanda air flow pattern.

Outdoor Air

ASHRAE Standard 62-89 specifies that every commercial
space be provided with fifteen cfm per occupant of outdoor
air to replenish oxygen and dilute CO2. If other internal
sources of gaseous contamination are present, additional
outside air is needed to dilute the contamination.

EXAMPLE:

An office requires 20 cfm per person because
the standard estimates some smoking, some
copy machine operation, etc. The standard
assumes outdoor air will be cleaned to less
than 75 micrograms per cubic meter prior to
introduction into the space. ASHRAE Standard
62-89 states that supplemental air cleaning to
control smoke or additional outside air must
be provided as required.

Example 1. Sizing by Air Changes per Hour and Room Volume

An office measures 40 x 45 feet (12 x 14 meters) with a 15 foot (4.5 meter) ceiling. How many F90As should be installed?

Solution:

1. Find the room volume: 40 x 45 x 15 feet = 27,000 cubic feet, (12 x 14 x 4.5 meters = 756 cubic meters).
2. Assuming seven air changes per hour, with 27,000 cubic feet (756 cubic meters) volume, the graph below indicates three

F90As are required.

3. Clean outdoor air is also required to replenish oxygen and dilute gaseous contaminants. 20 cfm per person is required for

offices.

1

2

3

4

5

6

7

8

9

10

F90As REQUIRED

25

20

15

10

5

0

10,000

[283]

20,000

[567]

30,000

[850]

40,000

[1133]

50,000

[1416]

60,000

[1700]

70,000

[1983]

ROOM VOLUME IN CUBIC FEET AND [CUBIC METERS]

CAFETERIAS

LUNCHEONETTES

BARS

RESTAURANTS

STORES

OFFICES

BOWLING
CENTERS

PLACES OF

ASSEMBLY

M1524

AIR

CHANGES

PER HOUR